On the study of an energy-efficient greenhouse for heating, cooling and dehumidification applications
An analytical model, based on basic heat-transfer processes within a greenhouse, was used to study the performance of heat pump to meet the heating and dehumidification requirements in a greenhouse. Performance parameters of the heat pump, namely the Coefficient of Performance (COP) and the Specific Energy Consumption (SEC) of the heat pump were determined, along with the condenser and evaporator capacity ratings required to provide the necessary thermal conditioning to a model-sized greenhouse. Based on a typical weather pattern in Bangkok, the performance of the heat pump to maintain the greenhouse air at a day temperature of 27 °C and night temperature of 18 °C with a relative humidity of 40% spans 1.2-4.0 and 1000-16,000 kJ/kg for COP and SEC, respectively.
Year of publication: |
2004
|
---|---|
Authors: | Chou, S. K. ; Chua, K. J. ; Ho, J. C. ; Ooi, C. L. |
Published in: |
Applied Energy. - Elsevier, ISSN 0306-2619. - Vol. 77.2004, 4, p. 355-373
|
Publisher: |
Elsevier |
Keywords: | Greenhouse model Heat pump Coefficient of performance Specific energy consumption |