Moderately high temperature water source heat-pumps using a near-azeotropic refrigerant mixture
A ternary mixture of R124/R142b/R600a, named HTR01, for moderately high temperature heat pumps, was developed. Tests of material compatibility and oil miscibility showed that the mixture could be used with a R22 compressor in an HTR01 heat-pump system. A 2.92 kW moderately high temperature water source heat pump system was set up with HTR01 as the refrigerant to study the system performance with HTR01. Then, a 300 kW moderately high temperature water source heat pump system was built with HTR01 as the refrigerant to test the performance with a geothermal hot water source. The test showed that the condenser outlet water temperature could reach and hold on about 90 °C with a high coefficient of performance.
Year of publication: |
2005
|
---|---|
Authors: | Nanxi, Liu ; Shi, Lin ; Lizhong, Han ; Mingshan, Zhu |
Published in: |
Applied Energy. - Elsevier, ISSN 0306-2619. - Vol. 80.2005, 4, p. 435-447
|
Publisher: |
Elsevier |
Keywords: | Heat pumps Water source heat pump Refrigerant mixtures |